HomeMy WebLinkAbout1988 CC RESO 15,783RESOLUTION NO. 15,783
A RESOLUTION OF THE CITY COUNCIL
OF THE CITY OF NATIONAL CITY, CALIFORNIA,
ADOPTING TRASH REGEPTACLP ENCLOSURE
DESIGN GUIDELINES
BF IT RESOLVED by the City Council of the City of National City that
where trash receptacle enclosures are required for commercial, industrial,
institutional, or multifamily residential uses pursuant to Section 7.10.080
of the National City Municipal Code, the following standards shall apply:
1. PERMITS REQUIRED
Construction of all reinforced
shall require a site plan review
of a building permit by the City.
copies of a site plan showing,
enclosure in relation to existing buildings, property lines, street
and/or alley.
2. LOCATION
Trash receptacle enclosures shall not be located within 10-feet
of any window of any dwelling unit or within 5-feet of any
combustible wall.
B. Where enclosure is located within a parking facility, the area in
front of the required enclosure opening shall be clearly marked
"No Parking".
Where enclosure is located within any building or structure or
area wherein the trash receptacle is to be
provided with an approved floor drain
. Method of maintaining the
A.
C.
D.
portion thereof, the
maintained shall be
connected to the public sewer system
masonry trash receptacle enclosures
(See Chapter 18.128) and the issuance
The applicant shall submit two (2)
by dimension, proposed location of
receptacle within the immediate area of the floor drain shall be
subject to approval of the Director of Planning.
All enclosures shall be so located that the gates, when open, or
being opened, shall not project beyond any lot line. When said
gates open onto an alley, the wall or portion thereof containing
the gates shall be at least 5-feet form the line forming the
n boundary between the lot and the alley.
3. CONSTRUCTION
A. Commercial
t Rece tacles (Table I). Enclosure shall be
constructed of reinforced masonry with view obscuring gates of a
height sufficient to conceal the container used. Either 8-inch
slump or split -face block may be used. Standard 8-inch concrete
block is allowed provided that the exterior faces are painted or
otherwise finished to be compatible with the primary building on
the site. For restaurant use, interior faces must be covered
with a smooth stucco finish.
B. Individual minimum
30- llon containers (Table 2)• Enclosure
shall be constructed
of reinforr ed masonry with view obscuring
gates of a height sufficient to conceal the containers used.
Either 6 or 8 inch slump or split -face block may be used.
Standard 6 or 8 inch concrete block is allowed provided that the
exterior faces are painted or otherwise finished to be compatible
with the primary building on the site. For restaurant use,
interior faces must be covered with a smooth stucco finish.
Variation from width and/or length of enclosure shown in Table 2
may be permitted subject to approval by the Director of Planning.
PASSED AND ADOPTED this 1st day of November, 1988.
GEORGE H. WATERS, MAYOR
ATTEST:
IONE CAMPBELL, CITY CLERK
APPROVED AS TO FORM:
vJ
GEORGE H. EISEt, III -CITY ATTORNEY
TABLE 1
TRASH ENCLOSURE
SUBMIT ¶1W) (2) COPIES OF SITE PLAN SOWING THE PROPOSED LOCATION OF TRASH ENCLOSURE.
CONFLICTS WITH RESIDENTIAL UNITS AND PARKING SPACES SHALL BE AVOIDED. IF LOCATED ADJACENT
TO A PARKING AREA, THE AREA IN FRCNF OF THE ENCLOSURE OPENING SHALL BE CLEARLY MARKED "NO
PARKING". ALL ENCLOSURES SHALL BE LOCATED RC FACILITATE THE EMPTYING OF BINS BY DISPOSAL
SERVICE DQUIPMEN'r. ENCLOSURES SHALL NOT BE LOCATED WITHIN 10-r'i i 2 OF ANY W3NDOW IN ANY
DWELLING UNIT, OR WITHIN 5-rh r OF A COMBUSTIBLE WAIL.
TRASH ENCLOSURES SHALL BE OF A HEIGHT SUFFICIENT 'ID CONCEAL THE CONTAINER USED. SEE
ILLUSTRATIONS HERDON.
THE ATTACK DRAWING runSTRATES THE BASIC CONSTRUCTION REQUIRED. THE MINIMUM SIZE SHOWN
MAY NOT ACCOMMODATE YOUR TRASH BIN, THEREFORE, THE OWNER MUST DETERMINE THE SIZE PRIOR TO
COMMENCING CONSTRUCTION. MODIFICATIONS IN DESIGN MAY BE PERMIPrID WITH APPROVAL OF THE
DIREC1tR OF PLANNING.
•PLAN •SIDE ELEVATION
❑❑
❑❑
❑❑
❑❑
❑❑
❑u
113)
D-2
18" MINIMUM
118" MINMUM
b
1'MINIMUM
4-
I
�
i
i
(see note below
NOTES: USE OF SLUMP OR SPLIT FACE BLOCK IS
ENCOURAGED. STANDARD CONCRETE BLOCK WILL BE
ALLOW®, IF PAINTED, S' U(ooFD OR OTHERWISE
FINISHED TO BE COMPATIBLE WITH THE PRIMARY
BUILDING ON THE SITE, SUBJECT TO THE APPROVAL
OF THE PLANNING DIRECTOR. PLEASE INDICATE
TYPE OF BLOCK AND FINISH ON BUILDING PERMIT
APPLICATION.
See also attachments 1 and 2) Revised Sept; or 0988
•
Table 1 (Attahhment 1)
HEAVY DUTY STEEL GATE LATCH
DETAIL 1
0
Iu=11111M
7 11111—
SECTION 1
3/4' X4' ANCHOR BOLT
HEAVY DUTY LOOSE JOINT HINGE
TWO KNUCKLE/STEEL 31/2'MIN.
WELDED TO 1/8' FRAME &
1/4' STEEL PLATE
2'X4' BOLTED TO STEEL
FRAME W/ 1/4'X3' CARRIAGE BOLT
DETAIL 2
0es
0
Or
00
0'0
ii 4' CURB
rrimilet4' SLAB
rm111 2-#4 CONT. BARS
CAP BLOCK OR CEMENT CAP
b
8'CONC. BLOCK GROUT CELL WITH
STEEL BARS 18' ON 0/C
4 DOWELL AT 32' V. 0/C LAP 24' MIN.
SOLID GROUT END CELLS
1/4'X8' STEEL PLATE
PLYWOOD SIDING
(TEXTURE 5/8' TYPE 1-11)
/OR FINISHED METAL SIDING
Table 1 (Attachment 2)
2'X4' BOLTED TO STEEL
FRAME W/ 1/41')(3° CARRIAGE BOLT
HEAVY DUTY STEEL GATE LATCH
(see 0-1 for example)
1/4' STEEL PLATE
ANCHOR B4 LTED
TO BLOCK WALL
0
0
t o-
0
0
�j•
0
O 0
— 8' CONCRETE BLOCK
HEAVY DUTY LOOSE JOINT HINGE
TWO KNUCKLE/STEEL 31/2'MN.
WELDED TO 1/8' FRAME •
1/4' STEEL PLATE
1/e' STEEL FRAME
LATCH /VERTICAL ROD TYPE
FRONT ELEVATION
PLYWOOD SIDING
(TEXTURE 5/8' TYPE 1-11)
/ OR FINISHED METAL SUNG
41.
TRASH ENCLOSURE
TABLE 2
INDIVIDUAL. MINIMUM 30 GALLON CONTAINERS
SUBMIT TWO (2) COPIES OF SITE. PLAN SHOWING THE PROPOSED VOCATION OF TRASH ENaDSURE FOR
APPROVAL BY THE CITY. BUILDING PERMIT REQUIRED.
ENCLOSURES SHALL NOT BE LOCATED WITHIN 10-1• r e;tOF ANY %M ON IN ANY DWELLING UNIT, OR
WITHIN 5-FEKV OF A CON BUSTIffi. WALL.
TRASH ENCWASURES SHALL BE OF A HEIGHT SUFFICIENT TO CONCEAL THE CONTAINER USED. MINDEN
CONTAINER SIZE IS 30 GALLONS. SEE ILLUSTRATIONS HEREON.
THE ATTACHED DRAWING ILLUSTRATES THE BASIC OONSIRUCTION REQUIRED. THE MINIMUM SIZE SHOWN
MAY NOT AOOONNIODATE THE NUMBER CF CONTAINERS REQUIRED, THEREFORE, THE OWNER MUST DETERMINE
THE SIZE PRIOR TO OZWENCING OONSTRUCTICNc]. MODIFICATION IN DESIGN MAY BE PERMITTED WITH
APPROVAL CF THE DIRDCIOR OF PLANNING.
•PLAN
❑ ❑
o ado ❑
❑0100
❑ ❑
0
TYP. 30 GALLON
CONTAINER
D-2 7 8' MNMUM
0
a
2
D
z
z
•SIDE ELEVATION
(see note bebw
'OR8'
NOTES: USE OF SIB OR SPLIT FACE MIX IS
ENCOURAGED. STANDARD CONCREIE BLACK WILL BE
ALIENED, IF PAINTED, 5111CODED OR CHEMISE
FINISHED TO BE COMPATIBLE WITH 111E PRIMARY
BUILDING ON THE SITE, SUBJECP 10 THE APPROVAL
OF THE PLANNING DIREXROR. PLEASE INDICATE
TYPE OF BID ( AND FINISH CN BUILDING PERMIT
AP'LICATION.
ee also attachments 1 and 2) Revised Septe
,r
,1988
Table 2 (Attachment 1)
HEAVY DUTY STEEL GATE LATCH
DETAIL 1
0
CAP BLOCK OR CEMENT CAP
8' OR 8' BLOCK GROUT CELL WITH
STEEL BARS 18' ON 0/C
4 DOWELL AT 32' V. 0/C LAP 24' MIN.
SECTION 1
3/4' X4' ANCHOR BOLT
HEAVY DUTY LOOSE JOINT HINGE
TWO KNUCKLE/STEEL 31/2'M1N.
WELDED TO 1/8' FRAME &
1 /4' STEEL PLATE
2'X4' BOLTED TO STEEL
FRAME W/ 1/4'X3' CARRIAGE BOLT
DETAIL 2
II
4' SLAB
I 2-#4 CONT. BARS
SOLID GROUT END CELLS
1/4'X8' STEEL PLATE
PLYWOOD SIDING
(TEXTURE 5/8' TYPE 1-11)
/OR FINISHED METAL SONG
Table 2 (Attachment 2)
1/4' STEEL
ANCHOR
TO BLOC
PLATE
LTED
WALL
2'X4' BOLTED TO STEEL HEAVY DUTY STEEL GATE LATCH
FRAME W/ 1/4'X3' CARRIAGE BOLT (see D-1 for example)
— S' CONCRETE BLOCK
HEAVY DUTY LOSE T HINGE
TWO KNUCKLE STEEL 031/2 AIN.
WELDED TO 1/S' FRAME S
1/4' STEEL PLATE
1/B' STEEL FRAME 1 PLYWOOD SIDING
(TEXTURE 5/8' TYPE 1-11)
LATCH /VERTICAL ROD TYPE /OR FINISHED METAL SING
FRONT ELEVATION